Measurement method KS Standard MF300 NC
MF300 1C
MF300 NC
MF300 1C
Lightweight
R Type
Heavyweight
SP Type
Lightweight
R Type
Heavyweight
SP Type
Material   Steel plate Steel plate Steel plate(Epoxy electro-deposition on inside and outside surface) Steel plate(Epoxy electro-deposition on inside and outside surface)
measure Size(mm)   500 x 500 500 x 500 500 x 500 500 x 500
Weight(kg) Electronic scale     ¡Ö5.7kg ¡Ö7.2kg
Length(mm) Measure length of each side with height gauge ¡Â ¡¾0.5 Suitable Suitable
Thickness(mm) Measure VC on corner 21mm¡¾0.3 21mm¡¾0.3 Suitable Suitable
Our standard
Angle(mm) Refer to Article 7, 3, 2 of KS F4760 ¡Â 0.5 £¼ 0.1 £¼ 0.1
Level(mm) Install on flat surface and measure with Height Gauge using indicator Below 1.0 at the periphery £¼ 0.3 £¼ 0.3
Below 2.0 at the center £¼ 0.5 £¼ 0.5
Pressure resistance Intensive load Install panel at pressure tester, add the load with compulsive pressure device of 50 mm at the center of panel, and measure sagging quantity at the back of panel 300kgf 500kgf 300kgf 500kgf
Test variation(mm) £¼ 2.5 £¼ 2.5 £¼ 1.8 £¼ 2.0
Panel variation after installing prop element £¼ 4.0 £¼ 4.0 £¼ 2.3 £¼ 2.5
Impact resistance
(Impact test)
Free fall above the center of panel at the height of 500mm for sand bag, 1000 mm for tree type pendulum(KS F4760) No crack or fissure Suitable Suitable
Leakage resistance(¥Ø) Refer to leakage resistance test of KS F4760 Suitable Suitable
Corrosion resistance Refer to leakage resistance test of KS F4760 Adhesion level over 4 BNo variation or coming off by salt spray test Suitable Suitable
Conduction Refer to conduction performance test of KS F4760 Vp < 3000V Suitable Suitable
Conduction (Pressure acceleration) No problem over 1,000 Gal(based on Japanese Public Architecture Association)
  Measurement method KS Standard MF610S
Heavyweight
SP Type
Heavyweight
SP Type
Material   Steel plate Steel plate(Epoxy electro-deposition on inside and outside surface)
measure Size(mm)   610 x 610 610 x 610
Weight(kg) Electronic scale   ¡Ö9.85kg
Length(mm) Measure length of each side with height gauge ¡Â ¡¾0.5 Suitable
Thickness(mm) Measure VC on corner 33mm¡¾0.3mm
Our standard
Suitable
Angle(mm) Refer to Article 7, 3, 2 of KS F4760 ¡Â 0.6 £¼ 0.3
Level(mm) Install on flat surface and measure with Height Gauge using indicator Below 1.0 at the periphery £¼ 0.5
Below 2.0 at the center £¼ 0.7
Pressure resistance Intensive load Install panel at pressure tester, add the load with compulsive pressure device of 50 mm at the center of panel, and measure sagging quantity at the back of panel 500kgf 500kgf
Test variation(mm) £¼ 2.5 £¼ 2.3
Panel variation after installing prop element £¼ 4.0 £¼ 3.5
Impact resistance
(Impact test)
Free fall above the center of panel at the height of 500mm for sand bag, 1000 mm for tree type pendulum(KS F4760) No crack or fissure Suitable
Leakage resistance(¥Ø) Refer to leakage resistance test of KS F4760 Suitable
Corrosion resistance Refer to leakage resistance test of KS F4760 Adhesion level over 4 BNo variation or coming off by salt spray test Suitable
Conduction Refer to conduction performance test of KS F4760 Vp < 3000V Suitable
Conduction (Pressure acceleration) No problem over 1,000 Gal(based on Japanese Public Architecture Association)
Installation Method
(1) You can install it in Stringer type.
(2) MF600 series can be supplied in panel completed by attaching finishing materials such as vinyl tile and HPL at factory.